| Installation type/mounting |
| Mounting | on 35 mm DIN rail, 2 spacing units wide |
| Supply voltage |
| Rated value (DC) | |
| ● 24 V DC | Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Digital inputs |
| Number of digital inputs | 4 |
| Input voltage |
| ● Type of input voltage | DC |
| ● for signal "0" | < 5 V DC |
| ● for signal "1" | > 12 V DC |
| Input current |
| ● for signal "0", max. (permissible quiescent current) | 0.88 mA |
| ● for signal "1", typ. | 2.1 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — at "0" to "1", max. | 1.5 ms |
| — at "1" to "0", max. | 1.5 ms |
| Digital outputs |
| Number of digital outputs | 4 |
| Short-circuit protection | Yes |
| Output current |
| ● for signal "1" rated value | 0.3 A |
| Parallel switching of two outputs |
| ● for uprating | No |
| Switching frequency |
| ● with resistive load, max. | 10 Hz |
| ● with inductive load, max. | 0.5 Hz |
| EMC |
| Emission of radio interference acc. to EN 55 011 |
| ● Limit class B, for use in residential areas | Yes |
| Degree and class of protection |
| IP degree of protection | IP20 |
| Standards, approvals, certificates |
| CE mark | Yes |
| CSA approval | Yes |
| UL approval | Yes |
| FM approval | Yes |
| developed in accordance with IEC 61131 | Yes |
| according to VDE 0631 | Yes |
| Marine approval | Yes |
| Ecological footprint |
| ● environmental product declaration | Yes |
| Global warming potential |
| — global warming potential, (total) [CO2 eq] | 59.1 kg |
| — global warming potential, (during production) [CO2 eq] | 5.82 kg |
| — global warming potential, (during operation) [CO2 eq] | 53.6 kg |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.373 kg |
| Ambient conditions |
| Ambient temperature during operation |
| ● min. | -20 °C; No condensation |
| ● max. | 55 °C |
| Dimensions |
| Width | 35.5 mm |
| Height | 90 mm |
| Depth | 58 mm |