| General information |
| Product type designation | DQ 8x24VDC/0.5A ST |
| HW functional status | from FS21 |
| Firmware version | V0.0 |
| ● FW update possible | No |
| usable BaseUnits | BU type A0 |
| Color code for module-specific color identification plate | CC02 |
| Product function |
| ● I&M data | Yes; I&M0 to I&M3 |
| ● Isochronous mode | No |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated from version | STEP 7 TIA V14 with HSP0222 / integrated as of TIA V15 |
| ● STEP 7 configurable/integrated from version | V5.5 SP3 with HSP0230 V7.0 / integrated as of V5.6 SP1 |
| ● PCS 7 configurable/integrated from version | V8.1 SP1 |
| ● PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| ● PROFINET from GSD version/GSD revision | GSDML V2.3 |
| Operating mode |
| ● DQ | Yes |
| ● DQ with energy-saving function | No |
| ● PWM | No |
| ● Oversampling | No |
| ● MSO | No |
| Supply voltage |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Input current |
| Current consumption, max. | 20 mA; without load |
| output voltage / header |
| Rated value (DC) | 24 V |
| Power loss |
| Power loss, typ. | 1 W |
| Address area |
| Address space per module |
| ● Address space per module, max. | 1 byte; + 1 byte for QI information |
| Hardware configuration |
| Automatic encoding | Yes |
| ● Mechanical coding element | Yes |
| ● Type of mechanical coding element | Type A |
| Selection of BaseUnit for connection variants |
| ● 1-wire connection | BU type A0 |
| ● 2-wire connection | BU type A0 |
| ● 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| ● 4-wire connection | BU type A0 + Potential distributor module |
| Digital outputs |
| Type of digital output | Source output (PNP, current-sourcing) |
| Number of digital outputs | 8 |
| Current-sinking | No |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | Yes |
| output type acc. to IEC 61131, type 0.5 | Yes |
| Short-circuit protection | Yes; Electronic |
| ● Response threshold, typ. | 1 A; 0.7 to 1.3 A |
| Open-circuit detection | Yes |
| Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) |
| Controlling a digital input | Yes |
| Switching capacity of the outputs |
| ● with resistive load, max. | 0.5 A |
| ● with inductive load, max. | 0.5 A |
| ● on lamp load, max. | 5 W |
| Load resistance range |
| ● lower limit | 48 Ω |
| ● upper limit | 12 kΩ |
| Output current |
| ● for signal "1" rated value | 0.5 A |
| ● for signal "1" permissible range, max. | 0.5 A |
| ● for signal "0" residual current, max. | 0.1 mA |
| Output delay with resistive load |
| ● "0" to "1", max. | 50 µs; at rated load |
| ● "1" to "0", max. | 100 µs; at rated load |
| Parallel switching of two outputs |
| ● for uprating | No |
| ● for redundant control of a load | Yes |
| Switching frequency |
| ● with resistive load, max. | 100 Hz |
| ● with inductive load, max. | 0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads" |
| ● on lamp load, max. | 10 Hz |
| Total current of the outputs |
| ● Current per channel, max. | 0.5 A |
| ● Current per module, max. | 4 A |
| Total current of the outputs (per module) |
| horizontal installation |
| — up to 60 °C, max. | 4 A |
| vertical installation |
| — up to 50 °C, max. | 4 A |
| Cable length |
| ● shielded, max. | 1 000 m |
| ● unshielded, max. | 600 m |
| Interrupts/diagnostics/status information |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Alarms |
| ● Diagnostic alarm | Yes |
| Diagnoses |
| ● Monitoring the supply voltage | Yes |
| ● Wire-break | Yes; Module-wise |
| ● Short-circuit to M | Yes; Module-wise |
| ● Short-circuit to L+ | Yes; Module-wise |
| ● Group error | Yes |
| Diagnostics indication LED |
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| ● Channel status display | Yes; green PWR LED |
| ● for channel diagnostics | No |
| ● for module diagnostics | Yes; green PWR LED |
| Potential separation |
| Potential separation channels |
| ● between the channels | No |
| ● between the channels and backplane bus | Yes |
| ● Between the channels and load voltage L+ | No |
| Isolation |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates |
| Suitable for safety functions | No |
| Suitable for safety-related tripping of standard modules | No |
| Ecological footprint |
| ● environmental product declaration | Yes |
| Global warming potential |
| — global warming potential, (total) [CO2 eq] | 20.4 kg |
| — global warming potential, (during production) [CO2 eq] | 3.16 kg |
| — global warming potential, (during operation) [CO2 eq] | 17.5 kg |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.221 kg |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. | -30 °C; < 0 °C as of FS02 |
| ● horizontal installation, max. | 60 °C |
| ● vertical installation, min. | -30 °C; < 0 °C as of FS02 |
| ● vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level |
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Dimensions |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weights |
| Weight, approx. | 30 g |
| Approvals / Certificates |