SIMATIC S7-1200 G2: failsafe compact CPU 1214FC DC/DC/DC; power supply: DC 20.4-28.8 V DC; onboard I/O: 14x DI 24 V DC; 10x DO 24 V DC; memory: program 300 KB data: 750 KB, retentivity: 20 KB

 

General information
Product type designationCPU 1214FC DC/DC/DC
Firmware versionV1.0
● FW update possibleYes
Product function
● I&M dataYes; I&M0 to I&M3
● SysLogYes
Engineering with
● Programming packageSTEP 7 V20 or higher
Supply voltage
Rated value (DC) 
● 24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)145 mA; CPU only
Current consumption, max.1 000 mA; CPU with all expansion modules
Inrush current, max.12 A; at 28.8 V DC
I²t0.5 A²·s
Output current
for backplane bus (5 V DC), max.1 600 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 VYes; L+ minus 4 V DC min.
● Short-circuit protectionYes
● Output current, max.400 mA
Power loss
Power loss, typ.3.5 W
Memory
Work memory
● integrated1 050 kbyte
● integrated (for program)300 kbyte
● integrated (for data)750 kbyte
Load memory
● integrated8 Mbyte
● Plug-in (SIMATIC Memory Card), max.32 Gbyte; with SIMATIC memory card
Backup
● presentYes
● maintenance-freeYes
● without batteryYes
CPU processing times
for bit operations, typ.37 ns; / instruction
for word operations, typ.30 ns; / instruction
for floating point arithmetic, typ.74 ns; / instruction
CPU-blocks
Number of elements (total)4 000; Blocks (OB, FB, FC, DB) and UDTs
OB
● Number of free cycle OBs100
● Number of time alarm OBs20
● Number of delay alarm OBs20
● Number of cyclic interrupt OBs20; with minimum OB 3x cycle of 1 ms
● Number of process alarm OBs50
● Number of DPV1 alarm OBs3
● Number of isochronous mode OBs1
● Number of startup OBs100
● Number of asynchronous error OBs4
● Number of synchronous error OBs2
● Number of diagnostic alarm OBs1
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.20 kbyte
Flag
● Size, max.8 kbyte; Size of bit memory address area
Local data
● per priority class, max.64 kbyte; max. 16 KB per block
Address area
Process image
● Inputs, adjustable1 kbyte
● Outputs, adjustable1 kbyte
Hardware configuration
Number of modules per system, max.10
Time of day
Clock
● Hardware clock (real-time)Yes
● Backup time480 h; Typical
● Deviation per day, max.2 s; at 25 °C
Digital inputs
Number of digital inputs14; Integrated
● of which inputs usable for technological functions8; HSC (High Speed Counting)
Source/sink inputYes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.14
Input voltage
● Rated value (DC)24 V
● for signal "0"5 V DC or 0.5 mA
● for signal "1"15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at "0" to "1", min.0.1 µs
— at "0" to "1", max.20 ms
for interrupt inputs
— parameterizableYes
for technological functions
— parameterizablesingle phase: 6 HSCs @ 100 kHz & 2 standard @ 30 kHz, quadrature phase: 6 HSCs @ 80 kHz & 2 standard @ 20 kHz
Cable length
● shielded, max.500 m; 50 m for technological functions
● unshielded, max.300 m; for technological functions: No
Digital outputs
Number of digital outputs10; 20 kHz or 100 kHz
● of which high-speed outputs4; 100 kHz (Qa.0 - Qa.3)
Limitation of inductive shutdown voltage toL+ (-40 V)
Switching capacity of the outputs
● with resistive load, max.0.5 A
● on lamp load, max.5 W
Output voltage
● for signal "0", max.0.1 V; with 10 kOhm load
● for signal "1", min.20 V
Output current
● for signal "1" rated value0.5 A
● for signal "0" residual current, max.10 µA
Output delay with resistive load
● "0" to "1", max.1 µs; of the pulse outputs (Qa.0 to Qa.3), max. 1.0 µs; of the standard outputs (Qa.4 to Qb.1), max. 50 µs;
● "1" to "0", max.3 µs; of the pulse outputs (Qa.0 to Qa.3), max. 3.0 µs; of the standard outputs (Qa.4 to Qb.1), max. 200 µs;
Switching frequency
● of the pulse outputs, with resistive load, max.100 kHz; 100 kHz max. (Qa.0 - Qa.3), 20 kHz max. (Qa.4 to Qb.1)
Relay outputs
● Number of relay outputs0
Cable length
● shielded, max.500 m
● unshielded, max.150 m
Analog inputs
Number of analog inputs0
Analog outputs
Number of analog outputs0
Encoder
Connectable encoders
● 2-wire sensorYes
1. Interface
Interface typePROFINET
IsolatedYes
automatic detection of transmission rateYes
AutonegotiationYes
AutocrossingYes
Interface types
● RJ 45 (Ethernet)Yes
● Number of ports2
● integrated switchYes
Protocols
● IP protocolYes; IPv4
● PROFINET IO ControllerYes
● PROFINET IO DeviceYes
● SIMATIC communicationYes
● Open IE communicationYes; Optionally also encrypted
● Web serverYes
● Media redundancyYes
PROFINET IO Controller
● Transmission rate, max.100 Mbit/s
Services
— PG/OP communicationYes; encryption with TLS V1.3 pre-selected
— Isochronous modeYes
— IRTYes
— PROFIenergyYes; per user program
— Prioritized startupYes
— Number of IO devices with prioritized startup, max.16
— Number of connectable IO Devices, max.31
— Of which IO devices with IRT, max.31
— Number of connectable IO Devices for RT, max.31
— of which in line, max.31
— Activation/deactivation of IO DevicesYes
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— Updating timeThe minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.
Update time for IRT
— for send cycle of 1 ms1 ms to 16 ms
— for send cycle of 2 ms2 ms to 32 ms
— for send cycle of 4 ms4 ms to 64 ms
Update time for RT
— for send cycle of 1 ms1 ms to 512 ms
— for send cycle of 2 ms2 ms to 512 ms
— for send cycle of 4 ms4 ms to 512 ms
PROFINET IO Device
Services
— PG/OP communicationYes; encryption with TLS V1.3 pre-selected
— Isochronous modeNo
— IRTYes
— PROFIenergyYes; per user program
— Shared deviceYes
— Number of IO Controllers with shared device, max.2
Protocols
Supports protocol for PROFINET IOYes
PROFIsafeYes
PROFIBUSNo
OPC UANo
AS-InterfaceNo
Protocols (Ethernet)
● TCP/IPYes
● DHCPYes
● SNMPYes
● DCPYes
● LLDPYes
Number of connections
● Number of connections, max.128; via integrated interfaces of the CPU and connected CPs / CMs
● Number of connections reserved for ES/HMI/web10
● Number of connections via integrated interfaces88
Redundancy mode
Media redundancy
— MRPYes; as MRP redundancy manager and/or MRP client
— MRPDYes
SIMATIC communication
● S7 routingNo
● S7 communication, as serverYes
● S7 communication, as clientYes
Open IE communication
● TCP/IPYes
— Data length, max.8 kbyte
— several passive connections per port, supportedYes
● ISO-on-TCP (RFC1006)Yes
— Data length, max.8 kbyte
● UDPYes
— Data length, max.2 kbyte; 1 472 bytes for UDP broadcast
● DHCPYes
● DNSYes
● SNMPYes
● DCPYes
● LLDPYes
● EncryptionYes; Optional
Web server
● supportedYes
● HTTPSYes
● web APIYes
— Number of sessions, max.30
● User-defined websitesYes
Further protocols
● MODBUSYes
communication functions / header
S7 communication
● supportedYes
● as serverYes
● as clientYes
● User data per job, max.See online help (S7 communication, user data size)
Number of connections
● overallPG Connections: 4 reserved; HMI Connections: 4 reserved / 82 max; S7 Connections: 78 max; Open User Connections: 78 max; Web Connections: 2 reserved / 80 max; Total Connections: 10 reserved / 88 max
S7 message functions
Number of login stations for message functions, max.32
Program alarmsYes
Number of configurable program messages, max.5 000
Number of loadable program messages in RUN, max.2 500
Number of simultaneously active program alarms 
● Number of program alarms600
● Number of alarms for system diagnostics100
● Number of alarms for motion technology objects160
Test commissioning functions
Status/control
● Status/control variableYes
● VariablesInputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
● ForcingYes
Diagnostic buffer
● presentYes
Traces
● Number of configurable Traces4
● Memory size per trace, max.512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LEDYes
● ERROR LEDYes
● MAINT LEDYes
Supported technology objects
Motion ControlYes
● Number of available Motion Control resources for technology objects800
● Required Motion Control resources 
— per speed-controlled axis40
— per positioning axis80
— per synchronous axis160
— per external encoder80
— per output cam20
— per cam track160
— per probe40
● Number of available Extended Motion Control resources for technology objects40
● Required Extended Motion Control resources 
— per cam (1 000 points and 50 segments)2; 1000 points and 1 segment
— for each set of kinematics30
● kinematics functions 
— kinematics with up to 4 interpolating axesYes
— kinematics with 5 or more interpolating axesNo
— user-defined kinematicsNo
— SIMATIC Safe KinematicsNo
● Positioning axis 
— Number of positioning axes at motion control cycle of 4 ms (typical value)10
— Number of positioning axes at motion control cycle of 8 ms (typical value)10
Integrated Functions
CounterYes
● Number of counters8
● Counting frequency, max.100 kHz; Ia.0 to Ia.5: 100 kHz (80 kHz in quadrature mode), Ia.6 to Ib.5: 30 kHz (20 kHz in quadrature mode)
Frequency measurementYes
PID controllerYes
Number of pulse outputs8; individually assigned to CPU and Signal Board
Limit frequency (pulse)100 kHz
Potential separation
Potential separation digital inputs
● Potential separation digital inputsYes; field side to logic: 707 V DC (type test)
● between the channelsNo
● Number of potential groups1
Potential separation digital outputs
● Potential separation digital outputsYes
● between the channelsNo
● Number of potential groups1
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2Yes
— Test voltage at air discharge8 kV
— Test voltage at contact discharge6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000-4-4Yes
● Interference immunity on signal cables acc. to IEC 61000-4-4Yes
Interference immunity against voltage surge
● Interference immunity on supply lines acc. to IEC 61000-4-5Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6Yes
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areasYes; Group 1
● Limit class B, for use in residential areasYes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
IP degree of protectionIP20
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
CE markYes
UL approvalYes
cULusYes
FM approvalNo
RCM (formerly C-TICK)Yes
KC approvalYes
Marine approvalNo
Ecological footprint
● environmental product declarationYes; type 2 acc. to ISO 14021
Global warming potential
— global warming potential, (total) [CO2 eq]68 kg
— global warming potential, (during production) [CO2 eq]14.4 kg
— global warming potential, (during operation) [CO2 eq]54.2 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.723 kg
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1PLe
● SIL acc. to IEC 61508SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in accordance with SIL3< 2.00E-05
— High demand/continuous mode: PFH in accordance with SIL3< 1.00E-09 up to an operational altitude of 3 000 m or < 2.00E-09 at an operating altitude greater than 3 000 m up to 5 000 m
product functions / security / header
signed firmware updateYes
Secure BootYes
safely removing dataNo
Ambient conditions
Free fall
● Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
● min.-20 °C; No condensation
● max.40 °C; at max. voltages and max. specifications
● horizontal installation, min.-20 °C; No condensation
● horizontal installation, max.60 °C; at rated voltages, 50 % of max. specification and alternate IO active
● vertical installation, min.-20 °C; No condensation
● vertical installation, max.50 °C; at rated voltages, 50 % of max. specification and alternate IO active
Ambient temperature during storage/transportation
● min.-40 °C
● max.70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min.540 hPa
● Operation, max.1 140 hPa
● Storage/transport, min.540 hPa
● Storage/transport, max.1 140 hPa
Altitude during operation relating to sea level
● Installation altitude, min.-1 000 m
● Installation altitude, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity
● Operation, max.95 %; no condensation
Vibrations
● Vibration resistance during operation acc. to IEC 60068-2-63.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz
● Operation, tested according to IEC 60068-2-6Yes
Shock testing
● tested according to IEC 60068-2-27Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Pollutant concentrations
● SO2 at RH < 60% without condensationS02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free
configuration / header
configuration / programming / header
Programming language
— LADYes; incl. failsafe
— FBDYes; incl. failsafe
— SCLYes
Know-how protection
● User program protection/password protectionYes
Access protection
● protection of confidential configuration dataYes
● Protection level: Write protectionYes
● Protection level: Read/write protectionYes
● Protection level: Write protection for FailsafeYes
● Protection level: Complete protectionYes
● User administrationYes; device-wide
● Number of users100
● Number of groups100
● Number of roles50
programming / cycle time monitoring / header
● adjustableYes
Dimensions
Width80 mm
Height125 mm
Depth100 mm
Weights
Weight, approx.352 g
Etiketler
6ES7214-1AF50-0XB0, 6ES7214-1AF50-0XB0 SIMATIC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact CPU, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact CPU 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact CPU 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact CPU DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe compact DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe CPU, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe CPU 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe CPU 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe CPU DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 failsafe DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact CPU, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact CPU 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact CPU 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact CPU DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 compact DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 CPU, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 CPU 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 CPU 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 CPU DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 G2 DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact CPU, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact CPU 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact CPU 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact CPU DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe compact DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe CPU, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe CPU 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe CPU 1214FC DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe CPU DCDCDC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe 1214FC, 6ES7214-1AF50-0XB0 SIMATIC S7-1200 failsafe 1214FC DCDCDC,
cultureSettings.RegionId: 0 cultureSettings.LanguageCode: TR
Çerez Kullanımı

Sizlere en iyi alışveriş deneyimini sunabilmek adına sitemizde çerezler(cookies) kullanmaktayız. Detaylı bilgi için sayfamızın footer kısmında sözleşmeler başlığı altında "BEMİRAL ENTEGRE KVKK Kişisel Veri Gizlilik, Saklama, İmha Politikası" ile "KVKK Aydınlatma Metni" ve "Çerez Politikası" dokümanlarını inceleyebilirsiniz.