| Supply voltage |
| Load voltage L+ |
| ● Rated value (DC) | 24 V |
| ● permissible range, lower limit (DC) | 20.4 V |
| ● permissible range, upper limit (DC) | 28.8 V |
| Input current |
| from load voltage L+ (without load), max. | 80 mA |
| from backplane bus 5 V DC, max. | 80 mA |
| Power loss |
| Power loss, typ. | 4.9 W |
| Digital outputs |
| Number of digital outputs | 16 |
| Short-circuit protection | Yes; Electronic |
| ● Response threshold, typ. | 1 A |
| Limitation of inductive shutdown voltage to | L+ (-53 V) |
| Controlling a digital input | Yes |
| Switching capacity of the outputs |
| ● on lamp load, max. | 5 W |
| Load resistance range |
| ● lower limit | 48 Ω |
| ● upper limit | 4 kΩ |
| Output voltage |
| ● for signal "1", min. | L+ (-0.8 V) |
| Output current |
| ● for signal "1" rated value | 0.5 A |
| ● for signal "1" permissible range for 0 to 40 °C, min. | 5 mA |
| ● for signal "1" permissible range for 0 to 40 °C, max. | 0.6 A |
| ● for signal "1" permissible range for 40 to 60 °C, min. | 5 mA |
| ● for signal "1" permissible range for 40 to 60 °C, max. | 0.6 A |
| ● for signal "1" minimum load current | 5 mA |
| ● for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load |
| ● "0" to "1", max. | 100 µs |
| ● "1" to "0", max. | 500 µs |
| Parallel switching of two outputs |
| ● for uprating | No |
| ● for redundant control of a load | Yes |
| Switching frequency |
| ● with resistive load, max. | 100 Hz |
| ● with inductive load, max. | 0.5 Hz |
| ● with inductive load (acc. to IEC 60947-5-1, DC13), max. | 0.5 Hz |
| ● on lamp load, max. | 10 Hz |
| Total current of the outputs (per group) |
| horizontal installation |
| — up to 40 °C, max. | 4 A |
| — up to 60 °C, max. | 3 A |
| vertical installation |
| — up to 40 °C, max. | 2 A |
| Cable length |
| ● shielded, max. | 1 000 m |
| ● unshielded, max. | 600 m |
| Interrupts/diagnostics/status information |
| Alarms | No |
| Diagnostics function | No |
| Alarms |
| ● Diagnostic alarm | No |
| Diagnoses |
| ● Wire-break | No |
| ● Short-circuit | No |
| ● Fuse blown | No |
| ● missing load voltage | No |
| Diagnostics indication LED |
| ● Rated load voltage PWR (green) | No |
| ● Fuse OK FSG (green) | No |
| ● Status indicator digital output (green) | Yes |
| Potential separation |
| Potential separation digital outputs |
| ● between the channels | Yes |
| ● between the channels, in groups of | 8 |
| ● between the channels and backplane bus | Yes; Optocoupler |
| Isolation |
| Isolation tested with | 500 V DC |
| connection method |
| required front connector | 20-pin |
| Dimensions |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights |
| Weight, approx. | 190 g |