SIMATIC S7-1500, digital input module DI 32x24 V DC HF, 32 channels in groups of 16; of which 2 inputs as counters can be used; input delay 0.05..20 ms input type 3 (IEC 61131); diagnostics; hardware interrupts: front connector (screw terminals or push-in) to be ordered separately

 

 

 

 

General information
Product type designationDI 32x24VDC HF
HW functional statusfrom FS04
Firmware versionV2.2.1
● FW update possibleYes
Product function
● I&M dataYes; I&M0 to I&M3
● Isochronous modeYes
● Prioritized startupYes
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionV13 SP1 / -
● STEP 7 configurable/integrated from versionV5.5 SP3 / -
● PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
● PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
● DIYes
● CounterYes
● OversamplingNo
● MSIYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.40 mA; 20 mA per group with 24 V DC supply
Power
Power consumption from the backplane bus1.1 W
Power loss
Power loss, typ.4.2 W
Digital inputs
Number of digital inputs32
Digital inputs, parameterizableYes
Source/sink inputP-reading
Input characteristic curve in accordance with IEC 61131, type 3Yes
Digital input functions, parameterizable
● Gate start/stopYes
● Freely usable digital inputYes
● Counter 
— Number, max.2
— Counting frequency, max.6 kHz; FS04 and FW V2.2.1 or higher
— Counting width32 bit
— Counting direction up/downUp
Input voltage
● Rated value (DC)24 V
● for signal "0"-30 to +5 V
● for signal "1"+11 to +30V
Input current
● for signal "1", typ.2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms
— at "0" to "1", min.0.05 ms
— at "0" to "1", max.20 ms
— at "1" to "0", min.0.05 ms
— at "1" to "0", max.20 ms
for interrupt inputs
— parameterizableYes
for technological functions
— parameterizableYes
Cable length
● shielded, max.1 000 m
● unshielded, max.600 m
Encoder
Connectable encoders
● 2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Isochronous mode
Filtering and processing time (TCI), min.80 µs; At 50 μs filter time
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
● Diagnostic alarmYes
● Hardware interruptYes
Diagnoses
● Monitoring the supply voltageYes
● Wire-breakYes; to I < 350 µA
● Short-circuitNo
Diagnostics indication LED
● RUN LEDYes; green LED
● ERROR LEDYes; red LED
● Monitoring of the supply voltage (PWR-LED)Yes; green LED
● Channel status displayYes; green LED
● for channel diagnosticsYes; red LED
● for module diagnosticsYes; red LED
Potential separation
Potential separation channels
● between the channelsYes
● between the channels, in groups of16
● between the channels and backplane busYes
● between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for safety functionsNo
Ecological footprint
● environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]18.9 kg
— global warming potential, (during production) [CO2 eq]12.1 kg
— global warming potential, (during operation) [CO2 eq]7.66 kg
— global warming potential, (after end of life cycle) [CO2 eq]-1.02 kg
product functions / security / header
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-30 °C; From FS05
● horizontal installation, max.60 °C
● vertical installation, min.-30 °C; From FS05
● vertical installation, max.40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.260 g
Approvals / Certificates

 

 

 

cultureSettings.RegionId: 0 cultureSettings.LanguageCode: TR
Çerez Kullanımı

Sizlere en iyi alışveriş deneyimini sunabilmek adına sitemizde çerezler(cookies) kullanmaktayız. Detaylı bilgi için sayfamızın footer kısmında sözleşmeler başlığı altında "BEMİRAL ENTEGRE KVKK Kişisel Veri Gizlilik, Saklama, İmha Politikası" ile "KVKK Aydınlatma Metni" ve "Çerez Politikası" dokümanlarını inceleyebilirsiniz.