| General information |
| Product type designation | DQ 16x24VDC/0.5A BA |
| HW functional status | from FS01 |
| Firmware version | V1.0.0 |
| ● FW update possible | Yes |
| Product function |
| ● I&M data | Yes; I&M0 to I&M3 |
| ● Isochronous mode | No |
| ● Prioritized startup | Yes |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated from version | V13 / V13 |
| ● STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| ● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| ● PROFINET from GSD version/GSD revision | V2.3 / - |
| Operating mode |
| ● DQ | Yes |
| ● DQ with energy-saving function | No |
| ● PWM | No |
| ● Oversampling | No |
| ● MSO | Yes |
| Supply voltage |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; through internal protection with 7 A per group |
| Input current |
| Current consumption, max. | 30 mA |
| output voltage / header |
| Rated value (DC) | 24 V |
| Power |
| Power consumption from the backplane bus | 1.15 W |
| Power loss |
| Power loss, typ. | 2.2 W |
| Digital outputs |
| Type of digital output | Transistor |
| Number of digital outputs | 16 |
| Current-sourcing | Yes |
| Digital outputs, parameterizable | No |
| output type acc. to IEC 61131, type 0.5 | Yes |
| Short-circuit protection | Yes |
| ● Response threshold, typ. | 1 A |
| Limitation of inductive shutdown voltage to | L+ (-53 V) |
| Controlling a digital input | Yes |
| Switching capacity of the outputs |
| ● with resistive load, max. | 0.5 A |
| ● on lamp load, max. | 5 W |
| Load resistance range |
| ● lower limit | 48 Ω |
| ● upper limit | 12 kΩ |
| Output voltage |
| ● for signal "1", min. | L+ (-0.8 V) |
| Output current |
| ● for signal "1" rated value | 0.5 A |
| ● for signal "1" permissible range, max. | 0.5 A |
| ● for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load |
| ● "0" to "1", max. | 100 µs |
| ● "1" to "0", max. | 500 µs |
| Parallel switching of two outputs |
| ● for logic links | Yes |
| ● for uprating | No |
| ● for redundant control of a load | Yes |
| Switching frequency |
| ● with resistive load, max. | 100 Hz |
| ● with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 |
| ● on lamp load, max. | 10 Hz |
| Total current of the outputs |
| ● Current per channel, max. | 0.5 A; see additional description in the manual |
| ● Current per group, max. | 4 A; see additional description in the manual |
| ● Current per module, max. | 8 A; see additional description in the manual |
| Cable length |
| ● shielded, max. | 1 000 m |
| ● unshielded, max. | 600 m |
| Interrupts/diagnostics/status information |
| Diagnostics function | No |
| Substitute values connectable | No |
| Alarms |
| ● Diagnostic alarm | No |
| ● Maintenance interrupt | No |
| Diagnoses |
| ● Monitoring the supply voltage | No |
| ● Wire-break | No |
| ● Short-circuit | No |
| ● Group error | No |
| Diagnostics indication LED |
| ● RUN LED | Yes; green LED |
| ● ERROR LED | Yes; red LED |
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| ● Channel status display | Yes; green LED |
| ● for channel diagnostics | No |
| ● for module diagnostics | No |
| Potential separation |
| Potential separation channels |
| ● between the channels | No |
| ● between the channels, in groups of | 8 |
| ● between the channels and backplane bus | Yes |
| Isolation |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates |
| Siemens Eco Profile (SEP) | Siemens EcoTech |
| Suitable for safety functions | No |
| Suitable for safety-related tripping of standard modules | Yes; From FS02 |
| Ecological footprint |
| ● environmental product declaration | Yes |
| Global warming potential |
| — global warming potential, (total) [CO2 eq] | 43.8 kg |
| — global warming potential, (during production) [CO2 eq] | 9.5 kg |
| — global warming potential, (during operation) [CO2 eq] | 34.5 kg |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.231 kg |
| Highest safety class achievable for safety-related tripping of standard modules |
| ● Performance level according to ISO 13849-1 | PL d |
| ● Category according to ISO 13849-1 | Cat. 3 |
| ● SIL acc. to IEC 62061 | SIL 2 |
| ● remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/en/view/39198632 |
| product functions / security / header |
| signed firmware update | No |
| data integrity | No |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. | -30 °C; from FS04 |
| ● horizontal installation, max. | 60 °C |
| ● vertical installation, min. | -30 °C; from FS04 |
| ● vertical installation, max. | 40 °C |
| Altitude during operation relating to sea level |
| ● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Dimensions |
| Width | 25 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Weights |
| Weight, approx. | 230 g |
| Other |
| Note: | Supplied incl. 40-pole push-in front connectors |