SIMATIC S7-1500 analog input module AI 8xU/I/RTD/TC ST, 16 bit resolution, accuracy 0.3%, 8 channels in groups of 8; 4 channels for RTD measurement, common mode voltage 10 V; Diagnostics; Hardware interrupts; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately

 

General information
Product type designationAI 8xU/I/RTD/TC ST
HW functional statusFS04
Firmware versionV2.0.0
● FW update possibleYes
Product function
● I&M dataYes; I&M0 to I&M3
● Isochronous modeNo
● Prioritized startupNo
● Measuring range scalableNo
● Scalable measured valuesNo
● Adjustment of measuring rangeNo
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionV12 / V12
● STEP 7 configurable/integrated from versionV5.5 SP3 / -
● PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
● PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
● OversamplingNo
● MSIYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.255 mA; with 19.2 V supply
Encoder supply
24 V encoder supply
● Short-circuit protectionYes
● Output current, max.20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power consumption from the backplane bus0.7 W
Power loss
Power loss, typ.2.7 W
Analog inputs
Number of analog inputs8
● For current measurement8
● For voltage measurement8
● For resistance/resistance thermometer measurement4
● For thermocouple measurement8
permissible input voltage for voltage input (destruction limit), max.28.8 V
permissible input current for current input (destruction limit), max.40 mA
Constant measurement current for resistance-type transmitter, typ.150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Technical unit for temperature measurement adjustableYes; °C/°F/K
Input ranges (rated values), voltages
● 0 to +5 VNo
● 0 to +10 VNo
● 1 V to 5 VYes
— Input resistance (1 V to 5 V)100 kΩ
● -1 V to +1 VYes
— Input resistance (-1 V to +1 V)10 MΩ
● -10 V to +10 VYes
— Input resistance (-10 V to +10 V)100 kΩ
● -2.5 V to +2.5 VYes
— Input resistance (-2.5 V to +2.5 V)10 MΩ
● -25 mV to +25 mVNo
● -250 mV to +250 mVYes
— Input resistance (-250 mV to +250 mV)10 MΩ
● -5 V to +5 VYes
— Input resistance (-5 V to +5 V)100 kΩ
● -50 mV to +50 mVYes
— Input resistance (-50 mV to +50 mV)10 MΩ
● -500 mV to +500 mVYes
— Input resistance (-500 mV to +500 mV)10 MΩ
● -80 mV to +80 mVYes
— Input resistance (-80 mV to +80 mV)10 MΩ
Input ranges (rated values), currents
● 0 to 20 mAYes
— Input resistance (0 to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mAYes
— Input resistance (-20 mA to +20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type BYes
— Input resistance (Type B)10 MΩ
● Type CNo
● Type EYes
— Input resistance (Type E)10 MΩ
● Type JYes
— Input resistance (type J)10 MΩ
● Type KYes
— Input resistance (Type K)10 MΩ
● Type LNo
● Type NYes
— Input resistance (Type N)10 MΩ
● Type RYes
— Input resistance (Type R)10 MΩ
● Type SYes
— Input resistance (Type S)10 MΩ
● Type TYes
— Input resistance (Type T)10 MΩ
● Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer
● Cu 10No
● Cu 10 according to GOSTNo
● Cu 50No
● Cu 50 according to GOSTNo
● Cu 100No
● Cu 100 according to GOSTNo
● Ni 10No
● Ni 10 according to GOSTNo
● Ni 100Yes; Standard/climate
— Input resistance (Ni 100)10 MΩ
● Ni 100 according to GOSTNo
● Ni 1000Yes; Standard/climate
— Input resistance (Ni 1000)10 MΩ
● Ni 1000 according to GOSTNo
● LG-Ni 1000Yes; Standard/climate
— Input resistance (LG-Ni 1000)10 MΩ
● Ni 120No
● Ni 120 according to GOSTNo
● Ni 200 according to GOSTNo
● Ni 500No
● Ni 500 according to GOSTNo
● Pt 10No
● Pt 10 according to GOSTNo
● Pt 50No
● Pt 50 according to GOSTNo
● Pt 100Yes; Standard/climate
— Input resistance (Pt 100)10 MΩ
● Pt 100 according to GOSTNo
● Pt 1000Yes; Standard/climate
— Input resistance (Pt 1000)10 MΩ
● Pt 1000 according to GOSTNo
● Pt 200Yes; Standard/climate
— Input resistance (Pt 200)10 MΩ
● Pt 200 according to GOSTNo
● Pt 500Yes; Standard/climate
— Input resistance (Pt 500)10 MΩ
● Pt 500 according to GOSTNo
Input ranges (rated values), resistors
● 0 to 150 ohmsYes
— Input resistance (0 to 150 ohms)10 MΩ
● 0 to 300 ohmsYes
— Input resistance (0 to 300 ohms)10 MΩ
● 0 to 600 ohmsYes
— Input resistance (0 to 600 ohms)10 MΩ
● 0 to 3000 ohmsNo
● 0 to 6000 ohmsYes
— Input resistance (0 to 6000 ohms)10 MΩ
● PTCYes
— Input resistance (PTC)10 MΩ
Thermocouple (TC)
Temperature compensation
— parameterizableYes
— internal temperature compensationYes
— external temperature compensation via RTDYes
— Compensation for 0 °C reference point temperatureYes; fixed value can be set
— Reference channel of the moduleYes
Cable length
● shielded, max.800 m; for U/I, 200 m for R/RTD, 50 m for TC
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.16 bit
● Integration time, parameterizableYes
● Integration time (ms)2,5 / 16,67 / 20 / 100 ms
● Basic conversion time, including integration time (ms)9 / 23 / 27 / 107 ms
— additional conversion time for wire-break monitoring9 ms (to be considered in R/RTD/TC measurement)
— additional conversion time for resistance measurement150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms
● Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10 Hz
● Time for offset calibration (per module)Basic conversion time of the slowest channel
Smoothing of measured values
● parameterizableYes
● Step: NoneYes
● Step: lowYes
● Step: MediumYes
● Step: HighYes
Encoder
Connection of signal encoders
● for voltage measurementYes
● for current measurement as 2-wire transducerYes
— Burden of 2-wire transmitter, max.820 Ω
● for current measurement as 4-wire transducerYes
● for resistance measurement with two-wire connectionYes; Only for PTC
● for resistance measurement with three-wire connectionYes; All measuring ranges except PTC; internal compensation of the cable resistances
● for resistance measurement with four-wire connectionYes; All measuring ranges except PTC
Errors/accuracies
Linearity error (relative to input range), (+/-)0.02 %
Temperature error (relative to input range), (+/-)0.005 %/K; With TC type T 0.02 ± % / K
Crosstalk between the inputs, max.-80 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.02 %
Temperature error of internal compensation±6 °C
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-)0.3 %
● Current, relative to input range, (+/-)0.3 %
● Resistance, relative to input range, (+/-)0.3 %
● Resistance thermometer, relative to input range, (+/-)Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K
● Thermocouple, relative to input range, (+/-)Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)0.1 %
● Current, relative to input range, (+/-)0.1 %
● Resistance, relative to input range, (+/-)0.1 %
● Resistance thermometer, relative to input range, (+/-)Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K
● Thermocouple, relative to input range, (+/-)Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min.40 dB
● Common mode voltage, max.10 V
● Common mode interference, min.60 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
● Diagnostic alarmYes
● Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltageYes
● Wire-breakYes; Only for 1 to 5 V, 4 to 20 mA, TC, R, and RTD
● Overflow/underflowYes
Diagnostics indication LED
● RUN LEDYes; green LED
● ERROR LEDYes; red LED
● Monitoring of the supply voltage (PWR-LED)Yes; green LED
● Channel status displayYes; green LED
● for channel diagnosticsYes; red LED
● for module diagnosticsYes; red LED
Potential separation
Potential separation channels
● between the channelsNo
● between the channels, in groups of8
● between the channels and backplane busYes
● between the channels and the power supply of the electronicsYes
Permissible potential difference
between the inputs (UCM)20 V DC
Between the inputs and MANA (UCM)10 V DC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for applications according to AMS 2750Yes; Declaration of Conformity, see online support entry 109757262
Suitable for applications according to CQI-9Yes; Based on AMS 2750 E
Ecological footprint
● environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]38.6 kg
— global warming potential, (during production) [CO2 eq]14.4 kg
— global warming potential, (during operation) [CO2 eq]24.6 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.44 kg
product functions / security / header
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-25 °C; From FS08
● horizontal installation, max.60 °C
● vertical installation, min.-25 °C; From FS08
● vertical installation, max.40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.310 g
Other
Note:Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 ohms ±0.02%; resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermocouple: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K
cultureSettings.RegionId: 0 cultureSettings.LanguageCode: TR
Çerez Kullanımı

Sizlere en iyi alışveriş deneyimini sunabilmek adına sitemizde çerezler(cookies) kullanmaktayız. Detaylı bilgi için sayfamızın footer kısmında sözleşmeler başlığı altında "BEMİRAL ENTEGRE KVKK Kişisel Veri Gizlilik, Saklama, İmha Politikası" ile "KVKK Aydınlatma Metni" ve "Çerez Politikası" dokümanlarını inceleyebilirsiniz.