6ES7531-7NF00-0AB0 S7-1500, AI 8xU/I HF
6ES7531-7NF00-0AB0 S7-1500, AI 8xU/I HF
6ES7531-7NF00-0AB0 S7-1500, AI 8xU/I HF
6ES7531-7NF00-0AB0 S7-1500, AI 8xU/I HF
6ES7531-7NF00-0AB0 S7-1500, AI 8xU/I HF

6ES7531-7NF00-0AB0 S7-1500, AI 8xU/I HF

Fiyat : ₺54.255,53(KDV Dahil)
₺7.217,79 `den başlayan taksitlerle
SIMATIC S7-1500 analog input module AI 8xU/I HF, up to 24 bit resolution, accuracy 0.1%, 8 channels in groups of 1; common mode voltage: 30 V AC/60 V DC, Diagnostics; Hardware interrupts Measured values ​​scalable, measuring range adjustment, Calibrate in RUN; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately
General information
Product type designationAI 8xU/I HF
HW functional statusfrom FS01
Firmware versionV1.1.0
● FW update possibleYes
Product function
● I&M dataYes; I&M0 to I&M3
● Isochronous modeNo
● Prioritized startupYes
● Measuring range scalableNo
● Scalable measured valuesYes
● Adjustment of measuring rangeYes
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionV14 / -
● STEP 7 configurable/integrated from versionV5.5 SP3 / -
● PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
● PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
● OversamplingNo
● MSIYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.50 mA; with 24 V DC supply
Power
Power consumption from the backplane bus0.85 W
Power loss
Power loss, typ.1.9 W
Analog inputs
Number of analog inputs8
● For current measurement8
● For voltage measurement8
permissible input voltage for voltage input (destruction limit), max.28.8 V
permissible input current for current input (destruction limit), max.40 mA
Input ranges (rated values), voltages
● 0 to +5 VNo
● 0 to +10 VNo
● 1 V to 5 VYes
— Input resistance (1 V to 5 V)100 kΩ
● -10 V to +10 VYes
— Input resistance (-10 V to +10 V)100 kΩ
● -2.5 V to +2.5 VYes
— Input resistance (-2.5 V to +2.5 V)100 kΩ
● -25 mV to +25 mVNo
● -250 mV to +250 mVNo
● -5 V to +5 VYes
— Input resistance (-5 V to +5 V)100 kΩ
● -50 mV to +50 mVNo
● -500 mV to +500 mVNo
● -80 mV to +80 mVNo
Input ranges (rated values), currents
● 0 to 20 mAYes
— Input resistance (0 to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mAYes
— Input resistance (-20 mA to +20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type BNo
● Type CNo
● Type ENo
● Type JNo
● Type KNo
● Type LNo
● Type NNo
● Type RNo
● Type SNo
● Type TNo
● Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer
● Cu 10No
● Cu 10 according to GOSTNo
● Cu 50No
● Cu 50 according to GOSTNo
● Cu 100No
● Cu 100 according to GOSTNo
● Ni 10No
● Ni 10 according to GOSTNo
● Ni 100No
● Ni 100 according to GOSTNo
● Ni 1000No
● Ni 1000 according to GOSTNo
● LG-Ni 1000No
● Ni 120No
● Ni 120 according to GOSTNo
● Ni 200No
● Ni 200 according to GOSTNo
● Ni 500No
● Ni 500 according to GOSTNo
● Pt 10No
● Pt 10 according to GOSTNo
● Pt 50No
● Pt 50 according to GOSTNo
● Pt 100No
● Pt 100 according to GOSTNo
● Pt 1000No
● Pt 1000 according to GOSTNo
● Pt 200No
● Pt 200 according to GOSTNo
● Pt 500No
● Pt 500 according to GOSTNo
Input ranges (rated values), resistors
● 0 to 150 ohmsNo
● 0 to 300 ohmsNo
● 0 to 600 ohmsNo
● 0 to 3000 ohmsNo
● 0 to 6000 ohmsNo
● PTCNo
Cable length
● shielded, max.800 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.24 bit; When using the function "Scaling of the measured values" or "Measuring range adaptation" (32 bit REAL format); 16 bit when using the S7 format (16 bit INTEGER)
● Integration time, parameterizableYes
● Integration time (ms)Fast mode: 2.5 / 16.67 / 20 / 100 ms, standard mode: 7.5 / 50 / 60 / 300 ms
● Basic conversion time, including integration time (ms)Fast mode: 4 / 18 / 22 / 102 ms; Standard mode: 9 / 52 / 62 / 302 ms
● Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10 Hz
● Basic execution time of the module (all channels released)Corresponds to the channel with the highest basic conversion time
Smoothing of measured values
● parameterizableYes
● Step: NoneYes
● Step: lowYes
● Step: MediumYes
● Step: HighYes
Encoder
Connection of signal encoders
● for voltage measurementYes
● for current measurement as 2-wire transducerYes; with external transmitter supply
● for current measurement as 4-wire transducerYes
● for resistance measurement with two-wire connectionNo
● for resistance measurement with three-wire connectionNo
● for resistance measurement with four-wire connectionNo
Errors/accuracies
Linearity error (relative to input range), (+/-)0.02 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, max.-80 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.02 %
note regarding accuracyat temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-)0.1 %
● Current, relative to input range, (+/-)0.1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)0.05 %
● Current, relative to input range, (+/-)0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min.80 dB; in the Standard operating mode, 40 dB in the Fast operating mode
● Common mode voltage, max.60 V DC/30 V AC
● Common mode interference, min.80 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
● Diagnostic alarmYes
● Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltageYes
● Wire-breakYes; only for 1 ... 5 V and 4 ... 20 mA
● Overflow/underflowYes
Diagnostics indication LED
● RUN LEDYes; green LED
● ERROR LEDYes; red LED
● Monitoring of the supply voltage (PWR-LED)Yes; green LED
● Channel status displayYes; green LED
● for channel diagnosticsYes; red LED
● for module diagnosticsYes; red LED
Potential separation
Potential separation channels
● between the channelsYes
● between the channels, in groups of1
● between the channels and backplane busYes
● between the channels and the power supply of the electronicsYes
Permissible potential difference
between different circuits60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels
Isolation
Isolation tested with2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Ecological footprint
● environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]38.6 kg
— global warming potential, (during production) [CO2 eq]14.4 kg
— global warming potential, (during operation) [CO2 eq]24.6 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.44 kg
product functions / security / header
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-30 °C; From FS02
● horizontal installation, max.60 °C
● vertical installation, min.-30 °C; From FS02
● vertical installation, max.40 °C
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.280 g
Approvals / Certificates
cultureSettings.RegionId: 0 cultureSettings.LanguageCode: TR
Çerez Kullanımı

Sizlere en iyi alışveriş deneyimini sunabilmek adına sitemizde çerezler(cookies) kullanmaktayız. Detaylı bilgi için sayfamızın footer kısmında sözleşmeler başlığı altında "BEMİRAL ENTEGRE KVKK Kişisel Veri Gizlilik, Saklama, İmha Politikası" ile "KVKK Aydınlatma Metni" ve "Çerez Politikası" dokümanlarını inceleyebilirsiniz.