6ES7531-7QF00-0AB0 S7-1500, AI 8xU/I/R/RTD BA
6ES7531-7QF00-0AB0 S7-1500, AI 8xU/I/R/RTD BA
6ES7531-7QF00-0AB0 S7-1500, AI 8xU/I/R/RTD BA
6ES7531-7QF00-0AB0 S7-1500, AI 8xU/I/R/RTD BA
6ES7531-7QF00-0AB0 S7-1500, AI 8xU/I/R/RTD BA

6ES7531-7QF00-0AB0 S7-1500, AI 8xU/I/R/RTD BA

Fiyat : ₺27.952,24(KDV Dahil)
₺3.718,58 `den başlayan taksitlerle

SIMATIC S7-1500 Analog input module, AI 8xU/I/R/RTD BA, 16 bit resolution, Accuracy 0.5%, 8 channels in groups of 8; Common mode voltage 4 V DC, Diagnostics; Hardware interrupts; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately

 

General information
Product type designationAI 8xU/I/R/RTD BA
HW functional statusFS01
Firmware versionV1.0.0
● FW update possibleYes
Product function
● I&M dataYes; I&M0 to I&M3
● Isochronous modeNo
● Prioritized startupNo
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionV15.1 / V16
● STEP 7 configurable/integrated from versionV5.5 SP3 / -
● PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
● PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
● OversamplingNo
● MSIYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNNo
Power
Power consumption from the backplane bus0.85 W
Power loss
Power loss, typ.0.9 W
Analog inputs
Number of analog inputs8
● For current measurement8
● For voltage measurement8
● For resistance/resistance thermometer measurement8
permissible input voltage for voltage input (destruction limit), max.12 V; 12 V continuous, 30 V for max. 1 s
permissible input current for current input (destruction limit), max.40 mA
Constant measurement current for resistance-type transmitter, typ.230 ... 370 µA
Technical unit for temperature measurement adjustableYes; °C/°F/K
Input ranges (rated values), voltages
● 0 to +5 VNo
● 0 to +10 VNo
● 1 V to 5 VYes
— Input resistance (1 V to 5 V)10 MΩ
● -1 V to +1 VYes
— Input resistance (-1 V to +1 V)10 MΩ
● -10 V to +10 VYes
— Input resistance (-10 V to +10 V)10 MΩ
● -2.5 V to +2.5 VNo
● -25 mV to +25 mVNo
● -250 mV to +250 mVNo
● -5 V to +5 VYes
— Input resistance (-5 V to +5 V)10 MΩ
● -50 mV to +50 mVYes
— Input resistance (-50 mV to +50 mV)10 MΩ
● -500 mV to +500 mVYes
— Input resistance (-500 mV to +500 mV)10 MΩ
● -80 mV to +80 mVNo
Input ranges (rated values), currents
● 0 to 20 mAYes
— Input resistance (0 to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mAYes
— Input resistance (-20 mA to +20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type BNo
● Type CNo
● Type ENo
● Type JNo
● Type KNo
● Type LNo
● Type NNo
● Type RNo
● Type SNo
● Type TNo
● Type UNo
● Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer
● Cu 10No
● Cu 10 according to GOSTNo
● Cu 50No
● Cu 50 according to GOSTNo
● Cu 100No
● Cu 100 according to GOSTNo
● Ni 10No
● Ni 10 according to GOSTNo
● Ni 100Yes; Standard/climate
— Input resistance (Ni 100)10 MΩ
● Ni 100 according to GOSTNo
● Ni 1000Yes; Standard/climate
— Input resistance (Ni 1000)10 MΩ
● Ni 1000 according to GOSTNo
● LG-Ni 1000Yes; Standard/climate
— Input resistance (LG-Ni 1000)10 MΩ
● Ni 120No
● Ni 120 according to GOSTNo
● Ni 200No
● Ni 200 according to GOSTNo
● Ni 500No
● Ni 500 according to GOSTNo
● Pt 10No
● Pt 10 according to GOSTNo
● Pt 50No
● Pt 50 according to GOSTNo
● Pt 100Yes; Standard/climate
— Input resistance (Pt 100)10 MΩ
● Pt 100 according to GOSTNo
● Pt 1000Yes; Standard/climate
— Input resistance (Pt 1000)10 MΩ
● Pt 1000 according to GOSTNo
● Pt 200No
● Pt 200 according to GOSTNo
● Pt 500No
● Pt 500 according to GOSTNo
Input ranges (rated values), resistors
● 0 to 150 ohmsNo
● 0 to 300 ohmsNo
● 0 to 600 ohmsYes
— Input resistance (0 to 600 ohms)10 MΩ
● 0 to 3000 ohmsNo
● 0 to 6000 ohmsYes
— Input resistance (0 to 6000 ohms)10 MΩ
● PTCYes
— Input resistance (PTC)10 MΩ
Cable length
● shielded, max.200 m; 50 m at 50 mV
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.16 bit
● Integration time, parameterizableYes
● Integration time (ms)2,5 / 16,67 / 20 / 100 ms
● Basic conversion time, including integration time (ms)10 / 24 / 27 / 107 ms
— additional conversion time for wire-break monitoring4 ms (to be considered in R/RTD/U 1 to 5 V measurement)
— additional conversion time for resistance measurement8 ms
● Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10 Hz
Smoothing of measured values
● parameterizableYes
● Step: NoneYes
● Step: lowYes
● Step: MediumYes
● Step: HighYes
Encoder
Connection of signal encoders
● for voltage measurementYes
● for current measurement as 2-wire transducerYes; with external supply
● for current measurement as 4-wire transducerYes
● for resistance measurement with two-wire connectionYes; Only for PTC
● for resistance measurement with three-wire connectionYes; All measuring ranges except PTC; internal compensation of the cable resistances
Errors/accuracies
Linearity error (relative to input range), (+/-)0.1 %
Temperature error (relative to input range), (+/-)0.006 %/K
Crosstalk between the inputs, max.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.1 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-)0.5 %
● Current, relative to input range, (+/-)0.5 %
● Resistance, relative to input range, (+/-)0.5 %
● Resistance thermometer, relative to input range, (+/-)Ptxxx Standard: ±1.2 K, Ptxxx Climate: ±0.8 K, Nixxx Standard: ±0.8 K, Nixxx Climate: ±0.8 K
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)0.3 %
● Current, relative to input range, (+/-)0.3 %
● Resistance, relative to input range, (+/-)0.3 %
● Resistance thermometer, relative to input range, (+/-)Ptxxx Standard: ±1.0 K, Ptxxx Climate: ±0.5 K, Nixxx Standard: ±0.5 K, Nixxx Climate: ±0.5 K
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min.40 dB
● Common mode voltage, max.4 V
● Common mode interference, min.60 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
● Diagnostic alarmYes
● Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltageNo
● Wire-breakYes; Only for 1 ... 5 V, 4 ... 20 mA, R, and RTD
● Short-circuitNo
● Group errorNo
● Overflow/underflowYes
Diagnostics indication LED
● RUN LEDYes; green LED
● ERROR LEDYes; red LED
● MAINT LEDNo
● Monitoring of the supply voltage (PWR-LED)No
● Channel status displayYes; green LED
● for channel diagnosticsYes; red LED
● for module diagnosticsYes; red LED
Potential separation
Potential separation channels
● between the channelsNo
● between the channels, in groups of8
● between the channels and backplane busYes
Permissible potential difference
between the inputs (UCM)8 V DC
Between the inputs and MANA (UCM)4 V DC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP)Siemens EcoTech
Ecological footprint
● environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]38.6 kg
— global warming potential, (during production) [CO2 eq]14.4 kg
— global warming potential, (during operation) [CO2 eq]24.6 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.44 kg
product functions / security / header
signed firmware updateNo
data integrityNo
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-30 °C; From FS05
● horizontal installation, max.60 °C
● vertical installation, min.-30 °C; From FS05
● vertical installation, max.40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.250 g
cultureSettings.RegionId: 0 cultureSettings.LanguageCode: TR
Çerez Kullanımı

Sizlere en iyi alışveriş deneyimini sunabilmek adına sitemizde çerezler(cookies) kullanmaktayız. Detaylı bilgi için sayfamızın footer kısmında sözleşmeler başlığı altında "BEMİRAL ENTEGRE KVKK Kişisel Veri Gizlilik, Saklama, İmha Politikası" ile "KVKK Aydınlatma Metni" ve "Çerez Politikası" dokümanlarını inceleyebilirsiniz.