| Electrical connection type for auxiliary- and control-current circuit | Screw connection |
| Number of poles | Three-pole |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| Fitted with: | Suppressor circuit in actuating electronics |
| Operating frequency | 5000 mechanical Operations/h (DC operated) |
| Pollution degree | 3 |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78 |
| Connection to SmartWire-DT | In conjunction with DIL-SWD SmartWire DT contactor module Yes |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Utilization category | AC-3: Normal AC induction motors: starting, switch off during running AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
| Connection | Screw terminals |
| Frame size | FS2 |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient storage temperature - min | -40 °C |
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 2 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 10 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 5 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 10 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 20 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 25 HP |
| Conventional thermal current Ith (1-pole, enclosed) | 90 A |
| Conventional thermal current Ith (3-pole, enclosed) | 36 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 42 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 100 A |
| Equipment heat dissipation, current-dependent Pvid | 6.6 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 2.2 W |
| Switching time (DC operated, make contacts, closing delay) - max | 47 ms |
| Switching time (DC operated, make contacts, opening delay) - max | 30 ms |
| Application | Contactors for Motors |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Arcing time | 10 ms |
| Electrical connection type of main circuit | Screw connection |
| Screwdriver size | 2, Terminal screw, Pozidriv screwdriver 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
| Voltage type | DC |
| Degree of protection | IP00 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 1 |
| Number of contacts (normally closed) as main contact | 0 |
| Number of contacts (normally open contacts) | 1 |
| Number of main contacts (normally open contact) | 3 |
| Power consumption (pick-up) at DC | 12 W |
| Power consumption (sealing) at DC | 0.9 W |
| Rated breaking capacity at 220/230 V | 320 A |
| Rated breaking capacity at 380/400 V | 320 A |
| Rated breaking capacity at 500 V | 320 A |
| Rated breaking capacity at 660/690 V | 180 A |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 0 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 0 V |
| Drop-out voltage | 0.6 - 0.15 x UC, DC operated At least smoothed two-phase bridge rectifier or three-phase rectifier |
| Overvoltage category | III |
| Duty factor | 100 % |
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
| Lifespan, mechanical | 10,000,000 Operations (DC operated) |
| Pick-up voltage | 24 - 27 V DC (RDC 24) 0.7 - 1.2 V DC x Uc |
| Safe isolation | 440 V AC, Between coil and contacts, According to EN 61140 440 V AC, Between the contacts, According to EN 61140 |
| Screw size | M5, Terminal screw, Main cables M3.5, Terminal screw, Control circuit cables |
| Terminal capacity (stranded) | 1 x 16 mm², Main cables |
| Switching capacity (auxiliary contacts, general use) | 1 A, 250 V DC, (UL/CSA) 10 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | A600, AC operated (UL/CSA) P300, DC operated (UL/CSA) |
| Terminal capacity (flexible with ferrule) | 2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 16) mm², Main cables 2 x (0.75 - 10) mm², Main cables |
| Shock resistance | 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 5.3 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 6.9 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 3.5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Terminal capacity (solid) | 2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 4) mm², Control circuit cables 2 x (0.75 - 10) mm², Main cables 1 x (0.75 - 16) mm², Main cables |
| Terminal capacity (solid/stranded AWG) | Single 18 - 6, double 18 - 8, Main cables 18 - 14, Control circuit cables |
| Switching capacity (main contacts, general use) | 40 A, Maximum motor rating (UL/CSA) |
| Tightening torque | 3.2 Nm, Screw terminals, Main cables 1.2 Nm, Screw terminals, Control circuit cables |
| Rated control supply voltage (Us) at DC - max | 27 V |
| Rated control supply voltage (Us) at DC - min | 24 V |
| Rated insulation voltage (Ui) | 690 V |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 384 A |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 45 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 32 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 32 A |
| Rated operational current (Ie) at AC-3, 440 V | 32 A |
| Rated operational current (Ie) at AC-3, 500 V | 32 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 18 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 15 A |
| Rated operational current (Ie) at AC-4, 400 V | 15 A |
| Rated operational current (Ie) at AC-4, 440 V | 15 A |
| Rated operational current (Ie) at AC-4, 500 V | 15 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 12 A |
| Rated operational current (Ie) at DC-1, 110 V | 40 A |
| Rated operational current (Ie) at DC-1, 220 V | 40 A |
| Rated operational current (Ie) at DC-1, 60 V | 40 A |
| Rated operational current for specified heat dissipation (In) | 32 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 11 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 15 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 19 kW |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 4 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 4.5 kW |
| Rated operational power at AC-4, 380/400 V, 50 Hz | 7 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 7.5 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 8 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 9 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 10 kW |
| Rated operational power (NEMA) | 14.9 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Resistance per pole | 2.7 mΩ |
| Static heat dissipation, non-current-dependent Pvs | 0.9 W |
| Stripping length (control circuit cable) | 10 mm |
| Stripping length (main cable) | 10 mm |
| Short-circuit current rating (basic rating) | 5 kA, SCCR (UL/CSA) 125 A, max. Fuse, SCCR (UL/CSA) 125 A, max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 10/65 kA, CB, SCCR (UL/CSA) 10/100 kA, Fuse, SCCR (UL/CSA) 50/32 A, max. CB, SCCR (UL/CSA) 125/70 A, Class J, max. Fuse, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 10/100 kA, Fuse, SCCR (UL/CSA) 125/125 A, Class J, max. Fuse, SCCR (UL/CSA) 10/22 kA, CB, SCCR (UL/CSA) 50/32 A, max. CB, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 400 V | 125 A gG/gL |
| Suitable for | Also motors with efficiency class IE3 |
| Short-circuit protection rating (type 1 coordination) at 690 V | 63 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 63 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 35 A gG/gL |
| Special purpose rating of ballast electrical discharge lamps | 40 A (600V 60Hz 3phase, 347V 60Hz 1phase) 40 A (480V 60Hz 3phase, 277V 60Hz 1phase) |
| Special purpose rating of definite purpose rating | 192 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 32 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Special purpose rating of elevator control | 7.5 HP, 200 V 60 Hz 3-ph, (UL/CSA) 22 A, 240 V 60 Hz 3-ph, (UL/CSA) 22 A, 600 V 60 Hz 3-ph, (UL/CSA) 25.3 A, 200 V 60 Hz 3-ph, (UL/CSA) 7.5 HP, 240 V 60 Hz 3-ph, (UL/CSA) 20 HP, 480 V 60 Hz 3-ph, (UL/CSA) 20 HP, 600 V 60 Hz 3-ph, (UL/CSA) 27 A, 480 V 60 Hz 3-ph, (UL/CSA) |
| Special purpose rating of refrigeration control (CSA only) | 30 A, FLA 600 V 60 Hz 3phase; (CSA) 240 A, LRA 480 V 60 Hz 3phase; (CSA) 180 A, LRA 600 V 60 Hz 3phase; (CSA) 40 A, FLA 480 V 60 Hz 3phase; (CSA) |
| Special purpose rating of resistance air heating | 40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) 40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of tungsten incandescent lamps | 40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) 40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) |
| Conventional thermal current Ith at 40°C (3-pole, open) | 45 A |
| Conventional thermal current Ith at 50°C (3-pole, open) | 43 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 40 A |
| Rated operational power at AC-3, 440 V, 50 Hz | 20 kW |
| Rated operational power at AC-3, 500 V, 50 Hz | 23 kW |
| Rated operational power at AC-3, 690 V, 50 Hz | 17 kW |
| Actuating voltage | RDC 24: 24 - 27 V DC |
| Altitude | Max. 2000 m |
| Operating voltage at AC, 50 Hz - min | 24 V |
| Operating voltage at AC, 50 Hz - max | 690 V |
| Operating voltage at AC, 60 Hz - min | 24 V |
| Operating voltage at AC, 60 Hz - max | 690 V |