| Used with | Motor protective circuit-breaker |
| Features | Interlocked opposing contacts |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| Electric connection type | Screw connection |
| Pollution degree | 3 |
| Ambient operating temperature - max | 55 °C |
| Ambient operating temperature - min | -25 °C |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.04 W |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 1 |
| Number of contacts (normally open contacts) | 1 |
| Number of switches (fault signal) | 0 |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Mounting method | Side mounting |
| Overvoltage category | III |
| Control circuit reliability | < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Model | Top mounting |
| Lamp holder | None |
| Terminal capacity (solid/flexible with ferrule) | 0.75 - 1.5 mm² |
| Safe isolation | 440 V, Between auxiliary contacts and main contacts, According to EN 61140 |
| Rated operational current (Ie) | 1 A at AC-15, 440 V 500 V |
| Lifespan, electrical | 50,000 Operations |
| Switching capacity (auxiliary contacts, general use) | 1 A, 250 V DC, (UL/CSA) 5 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | Q300, DC operated (UL/CSA) A600, AC operated (UL/CSA) |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| Product category | Accessories |
| Short-circuit protection rating without welding | 10 A gG/gL, Fuse, Auxiliary contacts |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 3.5 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 2 A |
| Rated operational current (Ie) at DC-13, 110 V | 0.5 A |
| Rated operational current (Ie) at DC-13, 220 V, 230 V | 0.25 A |
| Rated operational current (Ie) at DC-13, 24 V | 2 A |
| Rated operational current (Ie) at DC-13, 60 V | 1 A |
| Rated operational current for specified heat dissipation (In) | 3.5 A |
| Rated operational voltage (Ue) at AC - max | 500 V |
| Rated operational voltage (Ue) at DC - max | 250 V |
| Terminal capacity (solid/stranded AWG) | 18 - 14, Screw terminals |